7, 12 & 15 kW SPECIFICATIONS
 |
 |
- Quiet, powerful Generac OHVI single-cylinder or V-Twin engines fueled by natural gas or LP gas.
- UL Listed remote-mounted pre-wired automatic transfer switch with 8, 10 or 12 circuit emergency load center for fast and efficient unattended transfer to generator when utility power fails.
- A standard weather protective enclosure with sound-absorbing panels protects generator from harmful weather and also reduces exterior noise levels. Includes key locks for security.
- Hinged top and removable front panel for easy serviceability.
- Built-in charger maintains battery at optimum performance level.
- Automatic safety shutdowns protect engine and generator in event of low oil pressure, high temperature, overspeed and/or overcrank.
- Automatic seven-day exerciser runs the system for twelve minutes weekly to maintain top running condition.
- Installation system includes the pre-wired automatic transfer switch with built-in load center, 30' and 2' wiring harnesses, pre-wired external connection box, 1' flexible fuel line, "Do-It-Yourself" installation guide and a composite mounting pad.
|
 |
|
 |
 |
 |
 |
 |
 |
Generator Set |
 |
 |
| Model Number |
04389 |
04456 |
04390 |
| Rated Power LP (kW) |
7 |
12 |
15** |
| Rated Power NG (kW) |
6 |
12 |
13 |
| Voltage @ 60 Hz |
120/240 |
120/240 |
120/240 |
| Phase |
Single |
Single |
Single |
| Frequency |
60 Hz |
60 Hz |
60 Hz |
| Amps LP |
58.3/29.2 |
100.0/50.0 |
125.0/62.5 |
| Amps NG |
50.0/25.0 |
100.0/50.0 |
108.3/54.2 |
| Engine/Alternator RPM |
3600/3600 |
3600/3600 |
3600/3600 |
| Engine |
410 cc.
14.5 HP
Generac OHVI
Single Cylinder |
992 cc.
30 HP
Generac OHVI
V-Twin |
992 cc.
30 HP
Generac OHVI
V-Twin |
| EPA/CARB Certified |
Yes |
Yes |
Yes |
| Fuel |
Natural Gas/
LP Vapor |
Natural Gas/
LP Vapor |
Natural Gas/
LP Vapor |
| Engine Cooling |
Air |
Air |
Air |
| UL2200 |
Yes |
Yes |
Yes |
| CSA Listed |
Yes |
Yes |
Yes |
| Main Line Circuit Breaker |
40 Amp |
50 Amp |
60 Amp |
| Dimensions (L" x W" x H") |
48 x 24 x 28-1/4 |
48 x 24 x 28-1/4 |
48 x 24 x 28-1/4 |
| Unit Wt. (lbs.) |
452 |
470 |
487 |
|
|
 |
 |
 |
 |
 |
 |
Controls |
 |
 |
| Start/Stop Control |
Cyclic cranking: 7 seconds on, 7 seconds rest. 90 seconds overcrank protection. |
| Automatic Low Oil Shutdown |
Standard |
| Overspeed Shutdown |
Standard, 72 Hz |
| Overcrank Protection |
Standard |
| Automatic Voltage Regulator with Over-Voltage Protection |
Standard |
| Engine Warmup |
10 seconds |
| Engine Cool-Down |
1 minute |
| Safety Fuse |
Standard |
| Starter Lockout |
Starter cannot re-engage until 5 seconds after the engine has stopped |
| 2 Amp Timed Trickle Battery Charger |
Standard |
| Auto Switch |
Utility failure/7 day exercise |
| Off Switch |
Stops unit. Power is removed. Control and charger still operate |
| Manual / test |
Start with starter control, unit stays on. If utility fails,transfer to load takes place |
|
|
 |
 |
 |
 |
 |
 |
Transfer Switch |
 |
 |
| No. of Poles |
2 |
| Current Rating (amps) |
100 |
| Voltage Rating (VAC) |
250 |
Utility Voltage Monitor (fixed)
Pick-up
Drop out |
80%
60% |
| Return to Utility |
Approx. 13 seconds |
| Exercises 7 minutes weekly |
Standard |
| UL Listed |
Standard |
| Dimensions (H" x W" x D") |
26.5 x 12.5 x 7 |
|
|
 |
| Go to 7, 12 & 15 kW specifications PDF |
 |