170 Ambassador Dr. Mississauga, Ontario L5T 2H9 - Phone: 905-670-2380 Email: info@bellcombustion.com
40 & 45 kW SPECIFICATIONS
 |
 |
- Quiet, powerful, liquid-cooled engine fueled by natural gas or LP.
- A standard weather protective enclosure protects generator from harmful weather and also effectively reduces exterior noise levels. Includes key locks for security.
- Built-in charger maintains battery at optimum performance level.
- Automatic safety shutdowns protect engine and generator in event of low oil level or pressure, high temperature, low coolant level, overspeed and/or overcrank.
- Automatic seven-day exerciser runs the system for fifteen minutes each week to maintain to running condition.
- Standard 200-amp remote-mounted automatic transfer switch for fast and efficient unattended transfer to generator when utility source fails. Housed in a NEMA 3R outdoor rated enclosure.
|
 |
|
 |
|
|
 |
 |
 |
 |
 |
 |
Controls |
 |
 |
| Start / Stop Control |
Cyclic cranking: 7 seconds on, 7 seconds rest. 90 seconds overcrank protection. |
| Automatic Low Oil Shutdown |
Standard |
| Overspeed Shutdown |
Standard, 70 Hz |
| Overcrank Protection |
Standard |
| Automatic Voltage Regulator with Over-Voltage Protection |
Standard |
| Engine Warmup |
15 seconds |
| Engine Cool-Down |
1 minute |
| Safety Fuse |
Standard |
| Starter Lockout |
Starter cannot re-engage until 5 seconds after engine has stopped |
| 2 Amp Timed Trickle Battery Charger |
Standard |
| Auto Switch |
Utility failure/7 day exercise |
| Off Switch |
Stops unit. Power is removed. Control and charger still operate |
| Manual / Test |
Start with starter control, unit stays on. If utility fails, transfer to load takes place |
|
|
 |
| 40 kW PDF Specification |
| 45 kW PDF Specification |
 |
| Top |
|
© 2006 bell combustion, Division of Al Bell Combustion Ltd.
|